Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
80
of 84
7.11
How do I log out of the GUI?
To log out of the ICT Hybrid Ultra GUI, click on the Logout link on the top
right of the browser window. The system will also automatically log off the
user after 20 minutes of inactivity.
8.0
PRODUCT SPECIFICATIONS
8.1
Electrical Specifications
Table 30. Overall Electrical Specifications
Parameters
Rating
AC Input Nominal Rating
120 / 240 VAC 50 / 60 Hz
AC Input Operating Range
108 to 264 VAC
AC Input Maximum Range
90 to 300 VAC
Input Power Factor (typical)
0.99 (120 VAC input)
Efficiency
Up to 95%
Output V Line Regulation
+/− 0.1%
Network Communication
RJ45 10/100-T port (IPv4, HTTP, HTTPS, SMTP, DNS,
TCP, UDP, ICMP, DHCP, ARP, SNMP v1/v2c/v3, SNTP
Protocols)
Network Security
Password protection, SSL encryption for HTTPS and
SMTP (TLS 1.2)
Table 31. Power Module Specifications
(cont’d on next page)
Parameters
Power
Chassis
ICT
700-
24PM
ICT
700-
48PM
ICT
1500-
24PM
ICT
1500-
48PM
AC Input Current (230 VAC)
<24 A
rms
3.5 A
max.
3.5 A
max.
8.0 A
max.
8.0 A
max.
AC Input Current (115 VAC)
<24 A
rms
7.0 A
max.
7.0 A
max.
8.0 A
max.
8.0 A
max.
Output Voltage
5
(Nominal
Battery float Voltage)
(+/
− 0.5%)
-
27.6
VDC
55.2
VDC
27.6
VDC
55.2
VDC
Output Voltage Range
(adjustable)
-
23
–31
VDC
46
–62
VDC
23
–31
VDC
46
–62
VDC
Output Power (max)
(230 VAC) @ N+1
6,000 W
700 W
700 W
1,500 W
1,500 W
Output Power (max)
(115 VAC) @ N+1
3,600 W
700 W
700 W
900 W
900 W