Alarm
Condition
Trigger Condition
Module
Output
1
Red
LED
Green
LED
Alarm
Relay
Send
2
PFC
Shutdown
Internal bus
voltage out of
range
Disabled
On
Off
No
-
Module Fault
Internal aux
voltages out of
range
Disabled
On
Off
Active
Yes
Over Temp
Shutdown
Internal temp too
high
Disabled
On
Off
Active
Yes
DC Output
Failure
Output above set
point (Manually re-
enable DC output
to reset)
Disabled
On
Off
Active
Yes
1
Other Power Modules are not affected when one module has its output disabled.
2
E-mail notifications only sent if enabled in the unit’s web-GUI E-mail Setup page, and either AC or DC
power is available for the system to be operational.
Table 19. Battery Management Module (BMM) Alarms
Alarm
Condition
Trigger Condition
LVD
Contactor
ICM
Required
Alarm
Relay
Send
2
Module Power
Failure
Loss of AC, and
battery disconnected
Open
No
-
Yes
No Alarms
Normal Operation
Closed
No
No
-
Battery Low
SOC
SOC drops below Low
SOC setting
Closed
Yes
Active
3
Yes
Battery
Overcurrent
Battery current rises
above overcurrent
setting for 10 s
Closed
Yes
Active
3
Yes
Circuit Breaker
Open
Circuit breaker trips or
manually opened
Open
Yes
Active
3
Yes
Battery Over
Temperature
Optional TMP probe
temp >50°C for 5 s
Open
Yes
Active
3
Yes
LVD
Battery V at LVD or
Overvoltage setting
Open
No
Active
Yes
Configuration
Error
BMM in wrong slot or
mixed polarity with
LDM
Open
No
Active
Yes
2
E-mail notifications only sent if enabled in the unit’s web-GUI E-mail Setup page, and either AC or DC
power is available for the system to be operational.
3
Contact active only if alarm enabled in the web-GUI module Setup page.