Secondary IP Address:
Set a secondary IP address for the unit to ping
to determine whether the network is functioning.
Watchdog Timeout:
Set a time in minutes (1–80 minutes) for the unit to
wait with no ping response from either IP address before initiating a
reset. The default is 10 minutes.
Reset Target:
Select what output to power cycle if the watchdog times
out. Set the Auto-Restart Delay time on the System, Settings & Control
tab to define how long the system will be off when the watchdog timeout
is triggered.
Selecting LDM Channel Outputs on a Hybrid Series 1RU units will have
no affect as there are no LDM channels on these products.
Data Logging
Data Logging:
Set the check box to Enable data logging. This will keep
a running record of all the key system parameters and alarms, recorded
once per minute for the last 30 days. The default is Disabled.
Log Starts Date:
Shows date and time that the data log started.
Clear Log Now:
Set the check box to clear the data log when you Save
Settings.
Download Log (CSV):
Click on the Download Log (CSV) button to store
the CSV format log file on the computer for further analysis.
NOTICE
Updating the firmware will delete the current log file. Download
the log before updating the firmware.
NOTE: Save Settings to enable any changes made.
4.8.2
NETWORK SETUP
Use this tab to configure the unit’s network settings.