Table 18. IMM2 error messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
If an action step is preceded by “(Trained technician only),” that step must be performed only by a trained
technician.
806f000f-220107xx
The System %1
encountered
firmware error -
unrecoverable
keyboard failure. (%1
=
ComputerSystem.ElementName)
Error
This message is for
the use case when
an implementation
has detected that
System Firmware
Error
Unrecoverable
Keyboard failure
has occurred.
1.
This is a UEFI detected event. The
UEFI diagnostic code for this event
can be found in the logged IMM
message text. Please refer to the
UEFI diagnostic code in the "UEFI
diagnostic code" section of the Info
Center for the appropriate user
response.
806f000f-22010axx
The System %1
encountered
firmware error - no
video device
detected. (%1 =
ComputerSystem.ElementName)
Error
This message is for
the use case when
an implementation
has detected that
System Firmware
Error No video
device detected has
occurred.
1.
This is a UEFI detected event. The
UEFI diagnostic code for this event
can be found in the logged IMM
message text. Please refer to the
UEFI diagnostic code in the "UEFI
diagnostic code" section of the Info
Center for the appropriate user
response.
806f000f-22010bxx
Firmware BIOS
(ROM) corruption
was detected on
system %1 during
POST. (%1 =
ComputerSystem.ElementName)
Error
Firmware BIOS
(ROM) corruption
was detected
during POST.
(Sensor = ABR
Status)
1.
Make sure the server meets the
minimum configuration to start
(see “Power-supply LEDs” on page
21).
2.
Recover the server firmware from
the backup page:
a.
Restart the server.
b.
At the prompt, press F3 to
recover the firmware.
3.
Update the server firmware to the
latest level (see “Updating the
firmware” on page 111).
Important:
Some cluster solutions
require specific code levels or
coordinated code updates. If the
device is part of a cluster solution,
verify that the latest level of code is
supported for the cluster solution
before you update the code.
4.
Remove components one at a time,
restarting the server each time, to
see if the problem goes away.
5.
If the problem remains, (trained
technician) replace the system
board.
208
System x3300 M4 Type 7382: Installation and Service Guide
Summary of Contents for System x3300 M4
Page 1: ...System x3300 M4 Type 7382 Installation and Service Guide...
Page 2: ......
Page 3: ...System x3300 M4 Type 7382 Installation and Service Guide...
Page 8: ...vi System x3300 M4 Type 7382 Installation and Service Guide...
Page 18: ...xvi System x3300 M4 Type 7382 Installation and Service Guide...
Page 44: ...26 System x3300 M4 Type 7382 Installation and Service Guide...
Page 128: ...110 System x3300 M4 Type 7382 Installation and Service Guide...
Page 156: ...138 System x3300 M4 Type 7382 Installation and Service Guide...
Page 382: ...364 System x3300 M4 Type 7382 Installation and Service Guide...
Page 405: ...Chapter 6 Removing and replacing components 387...
Page 450: ...432 System x3300 M4 Type 7382 Installation and Service Guide...
Page 454: ...436 System x3300 M4 Type 7382 Installation and Service Guide...
Page 468: ...450 System x3300 M4 Type 7382 Installation and Service Guide...
Page 469: ......
Page 470: ...Part Number 00V9709 Printed in USA 1P P N 00V9709...