Table 25. 101-711 through FFC-725 SRNs (continued)
SRN
FFC
Description and Action
651-786
304 214
Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-789
2CD 214
Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-78A
2CE 214
Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-78B
2CC 214
Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-809
Power fault warning due to unspecified cause.
Go to “Performing the checkout procedure” on page 184.
651-810
2E2
Over-voltage condition was detected.
Do the following procedure before replacing any FRUs:
1.
Shut the system down.
2.
Visually inspect the power cables and reseat the connectors.
3.
Run the following command diag -Avd sysplanar0. When the Resource Repair
Action menu displays, select
sysplanar0
.
651-811
2E2
Under voltage condition was detected
Do the following procedure before replacing any FRUs:
1.
Shut the system down.
2.
Visually inspect the power cables and reseat the connectors.
3.
Run the following command diag -Avd sysplanar0. When the Resource Repair
Action menu displays, select sysplanar0.
651-813
System shutdown due to loss of ac power to the site. System resumed normal
operation, no action required.
651-818
Power fault due to manual activation of power-off request. Resume normal
operation.
651-820
2E1
An over-temperature condition was detected.
1.
Make sure that:
v
The room ambient temperature is within the system operating environment
v
There is unrestricted air flow around the system
2.
Replace the system-board.
651-821
2E1
System shutdown due to an over maximum temperature condition being reached.
1.
Make sure that:
v
The room ambient temperature is within the system operating environment
v
There is unrestricted air flow around the system
2.
Replace the system-board.
651-822
2E1
System shutdown due to over temperature condition and fan failure. Use the
physical FRU location(s) as the probable cause(s). Use the physical location codes to
replace the FRUs that are identified on the diagnostics problem report screen.
651-831
2E2
Sensor detected a voltage outside of the normal range. Go to “Performing the
checkout procedure” on page 184.
651-832
G2E1
Sensor detected an abnormally high internal temperature. Make sure that:
1.
The room ambient temperature is within the system operating environment.
2.
There is unrestricted air flow around the system.
3.
There are no fan failures.
Chapter 2. Diagnostics
135