4-8
Service Guide
3. If the battery backup unit is installed, set the Master CB2 circuit breaker to On.
4. Set the Master CB1 circuit breaker to On.
Battery
Backup
Unit
Power
Distribution
Unit
Master
CB2
Master
CB1
Power
Distribution
Unit
Rear View of Rack
5. Close the back door of the system unit.
6. Plug all external device power cords into the electrical outlets.
7. Switch on power to all external devices attached to the system unit.
Note: Before setting the Power button to on, wait for the operator panel display to display
the word “Stand-By.”
8. Set the Power button to on (button pushed in).
Key Mode Switch
Normal
Secure
Service
Operator Panel
Power Button
Operator Panel Display
Summary of Contents for 7015-R30
Page 1: ...7015 Models R30 R40 and R50 CPU Enclosure Installation and Service Guide...
Page 10: ...x Service Guide...
Page 14: ...xiv Service Guide...
Page 34: ...1 20 Service Guide...
Page 214: ...6 10 Service Guide Detail 5 CPU Module 2 of 3 26 27 29 30 31 32 33 34 28 35...
Page 216: ...6 12 Service Guide Detail 6 CPU Module 3 of 3 36 37...
Page 252: ...B 8 Installation and Service Guide...
Page 288: ...Service Guide D 30...
Page 299: ......