• Do not over-tighten plumbing fittings or connections. This will cause leaks and might damage the
plumbing fittings.
• Use pipe dope on all threaded plumbing connections to ensure against leaks.
• Do not try to bend or reposition copper tubing. Excessive movement or bending of copper tubing might
damage the tubing and create leaks. If you find leaks, check all plumbing connections and fittings for
leaks before you connect power to the rack or any of the installed components.
• Repair all leaks before you connect power to the rack or any of the installed components.
• After the heat exchanger is filled, be sure to remove any excess water that might be left over from the
filling process.
• Plumbing components expand and contract with changing conditions and might fail or loosen after
installation. Place paper towels under the heat exchanger for a period of time; then, examine them for
signs of a leak. If it appears that there might be a leak, carefully inspect the entire heat exchanger to
determine whether there is a leak or whether it is water that is from the filling process.
• If the heat exchanger core or copper tubing is leaking or is damaged, remove it from the rack.
• New heat exchangers can be filled with pressurized nitrogen after assembly. Before you install the heat
exchanger, the nitrogen must be purged from the heat exchanger in a well-ventilated area. To purge the
nitrogen, remove the caps from the air-purging valves and press in on the valve stems to release the
nitrogen.
• When you install heat exchangers on a suite of racks, secure the racks together first; then, install the
heat exchangers.
The following graphic describes the parts required for rear door heat exchanger installation:
140 Power Systems: Racks and rack features
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...