8. Connect the cables that go between the racks.
9. If the racks are secured to a rack-mounting plate, torque the four bolts securing the rack to the rack
mounting plate to 54 - 67 newton-meters (40 - 50 foot-pounds), otherwise, go to step “11” on page
10. After the racks are bolted down install the airflow plate to the front of the racks. To install the airflow
plate, complete the following tasks:
a. Position the airflow plate so that it rests on the rack-mounting plate.
b. Install two M6x10 flathead screws.
c. Use a torque screwdriver to tighten each screw to 2.5 Nm ± 0.2 Nm (22.1 inch lb ± 1.8 lbs).
11. If necessary, install a side panel on the end rack. For more information, see “Installing the side
Attaching the stabilizer brackets
If the rack is not bolted to the floor, install the stabilizer bracket.
About this task
To attach the stabilizer bracket to the bottom of the rack, complete the following steps:
If you are connecting multiple racks for a 24-inch pitch, continue with “Connecting multiple racks with
600mm pitch, continue with “Connecting multiple racks with the rack-to-rack attachment kit for a 600
mm pitch” on page 114. If you are not connecting either, continue with the next step.
Procedure
1. Loosen the jam nut on each leveling foot (3) on each leveling foot, as shown in Figure 81 on page 117.
2. Rotate each leveling foot (3) downward until it contacts the surface on which the rack is placed, as
shown in Figure 81 on page 117.
3. Install the two mounting screws.
4. Adjust the leveling feet downward as needed until the rack is level. When the rack is level, tighten the
jam nuts against the base.
116 Power Systems: Racks and rack features
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...