Figure 102. Heat exchanger performance, 30kW heat load
*A given water temperature may be used only if the system that is supplying the water is able to measure
the room dew point and automatically adjust the water temperature accordingly. Otherwise, the water
temperature must be above the maximum dew point that is allowed at that data center installation.
The following graphic shows performance data for a 20 kW heat load. Because of the lower heat load, a
specific level of cooling can be achieved with warmer water, a lower flow rate, or both.
Racks and rack features 145