Figure 34. Reinstalling the cable channel cover
Item
Description
1
Cable channel cover
2
Terminal block (both sides)
3
Power distribution panel
4
Front of rack
Attaching the front or rear AC electrical outlet
If you need to attach an AC outlet, you can use the procedure in this section to perform this task.
Attention: The front and rear AC outlet-mounting plates mount through the same mounting holes
that secure the stabilizer brackets to the rack chassis. Therefore, if the rack must be bolted to the
floor, the stabilizer brackets must be removed.
Install the AC outlet-mounting plates only after the rack has been bolted to the floor and the stabilizer
brackets have been removed.
The following items are installed at the site:
• The AC outlet-mounting plate, which provides the mounting location for an AC electrical outlet.
• The AC electrical outlets on the front or rear of the rack.
• The ESD Y ground cable.
Note: you are responsible for providing both the outlets and the power cables that attach to the power
source. You are also responsible for connecting the AC outlet correctly. These items are not field-
replaceable units (FRUs).
Installing the AC outlet-mounting plates with AC outlets
If you choose to install AC mounting plates, perform the following tasks.
About this task
If you do not want to install AC outlets on the rack, go to “Installing the AC outlet-mounting plate without
48 Power Systems: Racks and rack features
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...