Figure 29. Circuit breaker removal (circuit breaker position shown is for reference only)
4. Pull the cover and circuit breaker assembly from the PDP.
5. Remove the 2 screws holding the cover to the circuit breaker.
6. If a circuit breaker with the same current rating is to be reinstalled, go to “Installing the system
component circuit breakers in the PDP” on page 37 and follow steps “2” on page 38 - 3.
7. Secure the circuit breaker by using the screw that you removed in step 3.
8. If you are replacing a circuit breaker, go to “Powering on the DC-powered system components” on
9. If you are installing a new circuit breaker with a different rating, go to “Installing the system
component circuit breakers in the PDP” on page 37.
10. If you are not installing a circuit breaker, install the circuit breaker cover by using the screw that you
removed in step 3.
11. Remove the current and EIA labels that are above the location from which the circuit breakers were
removed.
12. Repeat steps 1 - 11 for all the circuit breakers that you want to remove.
Removing the system component power cables from the PDP
To remove the -48V DC system component power cables from the PDP, use the following steps.
About this task
Note: Some system components may have the power supply identified alphabetically versus numerically.
Note: The device to be removed may only require either the A or B side circuit breaker to device cable to
be removed.
Racks and rack features 41
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...