35. Adjust the leveling feet downward as needed to take the load off the castors (ensure that they spin
freely) and until the rack is level. When the rack is level, tighten the jam nuts against the base of the
rack.
Figure 77. Adjusting the leveling feet
1
Rack front (base)
2
Leveling foot (quantity 4)
3
Jam nut (quantity 4)
36. If you have multiple racks that are connected in a suite (bolted to each other), go to “Connecting
multiple racks with rack-to-rack attachment kit for a 24-inch pitch” on page 112. If you are
connecting multiple racks for a 600 mm pitch, continue with “Connecting multiple racks with the
rack-to-rack attachment kit for a 600 mm pitch” on page 114. Otherwise, torque the four bolts to 54
- 67 newton-meters (40 - 50 foot-pounds).
37. After the rack is bolted down, install the airflow plate to the front of the rack. To install the airflow
plate, complete the following tasks:
a. Position the airflow plate (1) so that it rests on the rack-mounting plate.
b. Install two M6 x 10 flathead screws (2).
c. Use a torque screwdriver to tighten each screw to 2.5 Nm ± 0.2 Nm (22.1 inch lb ± 1.8 lbs).
Racks and rack features 111
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...