• (For fixed drawers.) This drawer is a fixed drawer and must not be moved for servicing unless
specified by the manufacturer. Attempting to move the drawer partially or completely out of the
rack might cause the rack to become unstable or cause the drawer to fall out of the rack. (R001
part 2 of 2)
Lift precautions:
Heat exchanger specifications
Heat exchanger specifications provide detailed information for your heat exchanger, including
dimensions, weight, temperature, and water information.
Table 2. Heat exchanger size and weight specifications
Size and weight
Specifications
Door size
Depth: 129 mm (5.0 in.)
Height: 1950 mm (76.8 in.)
Width: 600 mm (23.6 in.)
Door assembly weight
Empty: 39 kg (85 lb)
Filled: 48 kg (105 lb)
Table 3. Heat exchanger air specifications
Air
Specifications
Movement
Provided by servers and other devices in the rack
Temperature drop
With high-heat-load devices, up to 25°C (45°F)
between the air exiting the rack devices and the air
exiting the heat exchanger
Racks and rack features 143