2. Set the GlobalDelayTimer parameter with the object identifier (OID) as shown in the following
illustration.
3. Set the IndividualDelayTimer parameter with the OID.
Using Telnet through the Ethernet port
Set the parameters for the power-on sequence function by using an Ethernet port and the Telnet
interface.
About this task
To set the parameters for the power-on sequence function by using an Ethernet port and the Telnet
interface, complete the following steps:
Procedure
1. Log in as ADMIN/1001.
2. Type 1 for System Configuration.
3. Type 3 for Outlet Global Delay Timer and PDU Location.
4. Type 15 to define the Outlet Global Delay Timer.
5. Type the value for the New Outlet Global Delay Timer.
6. Type 0 to return to the previous menu.
7. Type 4 for the Outlet Name and Individual Delay Timer.
8. Type the outlet number and enter the outlet name and its IndividualDelayTimer value.
Using HyperTerminal through the serial port
Set the parameters for the power-on sequence function by using a serial port (HyperTerminal interface).
About this task
To set the parameters for the power-on sequence function by using a serial port (HyperTerminal
interface), complete the following steps:
Procedure
1. Make sure that the serial port configuration is 115200, 8-N-1-None.
2. Log-in as ADMIN/1001.
3. On the IBM PDU Configuration Utility main meu, type 8 to select Set PDU Location and Outlet
Information.
4. Ttype the GlobalDelayTimer value.
5. On the main menu, type the IndividualDelayTimer values for each outlet.
Using the web interface
Use the web interface to configure and monitor the PDU remotely. The PDU provides a graphical user
interface that you can view from a web browser. Using a web browser, you can access and monitor the
PDU power outlets and output devices remotely from a workstation or notebook computer.
Starting the web interface
To start the web interface, complete the following steps.
Procedure
1. Start a web browser from a workstation or notebook computer and enter the IP address of the PDU in
the address field. The Login window opens.
2. In the User Name field, type
ADMIN
(all uppercase letters). In the Password field, type
1001
.
3. Click Login. The main status page opens.
The main status page shows the PDU power outlets and input status per load segment:
Racks and rack features 75
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...