e. Ensure that the external -48 V DC return cable is routed correctly and installed on the return bus
bar.
Figure 31. Routing the power cables
Item
Description
1
-48 V DC power cable and return power cable
2
Power distribution panel
3
Front of rack
4
-48 V DC power cable and return power cable
Figure 32. Return bus bar
Item
Description
Item
Description
1
Front of power distribution
panel
6
(B) Return (-) power cable
2
(A) -48 V DC (-) bus bar
7
(B) -48 V DC (-) power cable
3
(A) -48 V DC (-) power cable
8
(B) Return (-) bus bar
4
(A) Return (-) bus bar
9
(B) -48 V DC (-) bus bar
5
(A) Return (-) power cable
f. If you want to install a power status alarm, connect the alarm cable to the terminal board on the
rear cover of the DC power distribution panel.
Note: Ensure that you remove the oxidation on the copper bus bars.
g. Ensure that the power-source ground cable is routed correctly and connects the power-source
ground cable to the copper bar at the lower-rear or upper-rear center of the rack.
46 Power Systems: Racks and rack features
Summary of Contents for 7014 T00
Page 1: ...Power Systems Racks and rack features IBM ...
Page 4: ...iv ...
Page 14: ...xiv Power Systems Racks and rack features ...
Page 151: ...Figure 98 Removing the remaining screws 7 Lift off the top cover Racks and rack features 137 ...
Page 167: ...Figure 110 Installing the inner hose panel Racks and rack features 153 ...
Page 184: ...170 Power Systems Racks and rack features ...
Page 195: ......
Page 196: ...IBM ...