N700E INSTRUCTION MANUAL
9-5
Note2 :Data value setting
Data value is transmitted except decimal point.
Ex1) Output frequency
Parameter value
Communication data
Conversion hexadecimal
60.0Hz
6000
1
st
byte : 0x17
2
nd
byte : 0x70
Ex2) acc/dec time
Parameter value
Communication data
Conversion hexadecimal
10.0sec
100
1
st
byte : 0x00
2
nd
byte : 0x64
Note3 :Special parameter
Run command
Parameter
1
st
byte : 0x00
2
nd
byte : 0x02
setting data
1
st
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
RST
REV
FWD
Bit 0 : Forward command
Bit 1 : Reverse command
Bit 2 : Reset command
Frequency command
Parameter
1
st
byte : 0x00
2
nd
byte : 0x04
setting data
output frequency * 100
Ex) the case of output frequency command is 60.00Hz
Data 6000 transmit
1
st
byte : 0x17
2
nd
byte : 0x70