N700E INSTRUCTION MANUAL
I
CAUTION FOR UL/cUL REQUIREMENTS
-THE HYUNDAI HEAVY INDUSTRY N700E INVERTER UL FILE NUMBER IS E205705.
CONFIRMATION OF UL LISTING CAN BE FOUND ON THE UL WEB SITE : www.ul.com
-DO NOT CONNECT OR DISCONNECT WIRING, OR PERFORM SIGNAL CHECKS WHILE
THE POWER SUPPLY IS TURNED ON.
-THERE ARE LIVE PARTS INSIDE THE INVERTER. NEVER TOUCH THE PRINTED WIRING
BOARD(PWB) WHILE THE POWER SUPPLY IS TURNED ON.
-[WARNING] THE BUS CAPACITOR DISCHARGE TIME IS 5 MINUTES. BEFORE STARTING WIRING OR
INSPECTION, SWITCH POWER OFF, WAIT FOR MORE THAN 5 MINUTES, AND CHECK FOR
RESIDUAL VOLTAGE BETWEEN TERMINAL P(+) AND N(-) WITH A METER ETC., TO AVOID HAZARD
OF ELECTRICAL SHOCK.
-[SHORT CIRCUIT RATING] THIS INVERTER IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF
DELIVERING NOT MORE THAN ___*1___ARMS SYMMETRICAL AMPERES, 480 VOLTS FOR HF TYPE
AND 240 VOLTS FOR LF TYPEMAXIMUM.
BRANCH CIRCUIT SHORT CIRCUIT PROTECTION SHALL BE PROVIDE BY FUSE ONLY
*1 see each Model for exact kA
5KA
N700E-055LF/075LFP ~ N700E-370HF/450HFP All Model
10KA
N700E-450HF/550HFP ~ N700E-1320HF/1600HFP All Model
18KA
N700E-1600HF/2000HFP ~ N700E-2200HF/2500HFP All Model
30KA
N700E-2800HF/3200HFP ~ N700E-3500HF/3800HFP All Model
-[OVER SPEED PROTECTION] THIS INVERTER DOES NOT PROVIDE OVER SPEED PROTECTION.
-[MOTOR OVER LOAD PROTECTION] THIS INVERTER PROVIDES MOTOR OVER LOAD
PROTECTION.OVER LOAD PROTECTION LEVEL IS 20~120% OF FULL LOAD CURRENT. THE
PROTECTION LEVEL MAY BE ADJUSTED BY CODE B04.REFER TO THE N700E USER GUIDE OR
CATALOG.
- [MOTOR OVERTEMPERATURE]MOTOR OVERTEMPERATURE SENSING IS NOT PROVIDED BY THE
DRIVE.
-[ENVIRONMENT]
MAXIMUM AMBIENT
TEMPERATURE
40℃
(WHEN CARRIER FREQUENCY EQUAL TO OR LESS THAN DEFAULT VALUE)
AMBIENT HUMIDITY
90% RH OR LESS(NO CONDENSING)
STORAGE
TEMPERATURE
-20~60
℃
VIBRATION
5.9
㎨
OR LESS
ALTITUDE
ALTITUDE 1,000m OR LESS
AMBIENCE
INDOORS(NO CORROSIVE AND FLAMMABLE GASES,
OIL MIST, DUST AND DIRT)
POLLUTION DEGREE
2