N700E INSTRUCTION MANUAL
2-7
Signal
Terminal
Symbol
Terminal name
Terminal function
Output
signal
RN0
RN1
Intelligent output terminal:
Run status signal(RUN), Frequency arrival signal(FA1),
Set frequency arrival signal(FA2),
Overload advance notice signal(OL),
PID error deviation signal(OD), Alarm signal(AL)
Contact rating:
AC 250V2.5A
(resistor load)
0.2A
(inductor load)
DC 30V 3.0A
(resistor load)
0.7A
(inductor load)
RN2
RN3
Intelligent
Output
signal
AL0
AL1
AL2
Alarm
output terminal:
Run status signal(RUN), Frequency arrival signal(FA1),
Set frequency arrival signal(FA2),
Overload advance notice signal(OL),
PID error deviation signal(OD), Alarm signal(AL)
Alarm output signals :
at normal status, power off : AL0-AL2 (closed)
at abnormal status : AL0-AL1(closed)
Contact rating:
AC 250V2.5A
(resistor load)
0.2A
(inductor load)
DC 30V 3.0A
(resistor load)
0.7A
(inductor load)
Table2-2Control circuit Terminals