N700E INSTRUCTION MANUAL
4-11
Func-
code
Name
Run-
time
Edit
Description
Defaults
Frequency-related Functions
A38
Frequency upperlimit
setting
X
Sets a limit on output frequency less than the
maximum frequency(A04). Range isfrequency lower
limit(A39) to maximum frequency(A04)in units of
0.01Hz.
0.00Hz
A39
Frequencylower limit
setting
X
Sets a limit on output frequency greater than zero.
Range is 0.00 to frequency upper limit(A38) in units
of 0.01Hz
0.00Hz
A40
A42
A44
Jump(center)frequency
setting
X
Up to 3 output frequencies can be defined for the
output to jump past to avoid motor resonances
(center frequency) range is 0.00 tomaximum
frequency(A04)in
units of 0.01Hz..
0.00Hz
A41
A43
A45
Jump(hysteresis)
frequency width
setting
X
Defines the distance from the center frequency at
which the jump around occurs.
Range is0.00 to 10.00Hz in units of 0.01Hz
0.00Hz
.