N700E INSTRUCTION MANUAL
5-6
5.3
Intelligent Input Terminal Function
Forward Run/Stop [FW] and Reverse Run/Stop Command [RV]
• When you input the Run command via the terminal [FW], the inverter executes the
Forward Runcommand (high) or Stop command(low)
• When you input the Run command via the terminal [RV], the inverter executes the
Reverse Run command(high) or Stop command(low).
Option
Code
Terminal
Symbol
Function Name
State
Description
0
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motorruns forward
OFF
Inverter is in Run Mode, motor stop
1
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motorruns reverse
OFF
Inverter is in Run Mode, motorruns stop
Valid for inputs:
Required setting
C01,C02,C03,C04,
C05,C06
Example:
A02=01
Notes:
• When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
• When a terminal associated with either[FW] or
[RV] function is configured fornormally closed,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
Set the parameterA02 to 1
DANGER : If the power is turned on and the Run command is alreadyactive, the motor starts
rotation and is dangerous! Before turning power on,confirm that Run command is not active.