N700E INSTRUCTION MANUAL
4-8
4.2.4
Expanded Function Mode of A Group
Func-
code
Name
Run-
time
Edit
Description
Defaults
Basic parameter settings
A01
Frequency command
(Multi-speedcommand
method)
X
Four options: select codes:
0.... Keypad potentiometer
1.... Control terminal input
2.... Standard operator
3.... Remote operator(1
ST
communication-RJ45)
4.... Remote operator(2
ND
communication-terminal)
1
A02 Run command
X
Set the method of run commanding:
0.... Standard operator
1.... Control terminal input
2.... Remote operator(1
ST
communication-RJ45)
3.... Remote operator(2
ND
communication-terminal )
1
A03 Base frequency setting
X
Settable from 0 to maximum frequencyin units of
0.01Hz
60.00Hz
A04
Maximum frequency
setting
X
Settable from the base frequency [A03]
up to 400Hz in units of 0.01 Hz.
In the case of sensorless vector control,
possible for driving to 300Hz
60.00Hz
Analog Input Settings
A05
External frequencysetting
start (O, OI)
X
Start frequency provided when analog
input is 0V (4mA) can be set in
units of 0.01Hz setting range is 0 to maximum
frequency(A04)
0.00Hz
A06
External frequencysetting
end (O, OI)
X
End frequency provided when analog
input is 10V(20mA) can be set in units
of 0.01Hz. setting range is 0 to maximum
frequency(A04)
0.00Hz
A07
External frequencystart rate
setting (O, OI)
X
The starting point(offset) for the active
analog input range(0
∼
10V, 4mA
∼
20mA)
setting range is 0 to 100% in units of 0.1%
0.0%
A08
External frequencyend rate
setting (O, OI)
X
The ending point(offset) for the active
analog input range(0
∼
10V, 4mA
∼
20mA)
setting range is 0 to 100% in units of 0.1%
100.0%