N700E INSTRUCTION MANUAL
4-23
Footnotes for the preceding tables
Note7:Carrier frequency factory setting in types of Inverter load and model.
Model
Heavy Duty (b26 = 0)
Normal Duty (b26 = 1)
N700E-055LF/075LFP~185LF/220LFP
N700E-055HF/075HFP~185HF/220HFP
5.0kHz
2.0kHz
N700E-220LF
N700E-220HF/300HFP~1320HF/1600HFP
3.0kHz
2.0kHz
N700E-1600HF/2000HFP~3500HF/3800HFP
2.0kHz
2.0kHz
※
By setting up b26=1, All models have the same carrier frequency2.0kHz.
Note8 : Carrier frequency ranges of different inverter types
Model
Range(kHz)
N700E-055LF/075LFP~150LF/185LFP
N700E-055HF/075HFP~150HF/185HFP
1.0 ~16.0
N700E-185LF/220LFP~220LF
N700E-185HF/220HFP~1320HF/1600HFP
1.0 ~10.0
N700E-1600HF/2000HFP~3500HF/3800HFP
1.0~4.0
※
If N700E-1600HF/2000HFP~3500HF/3800HFPare used more than 2kHz carrier frequency, they must
derate as much as 5%/kHz of rated current.