N700E INSTRUCTION MANUAL
5-2
Terminal
symbol
Terminal
name
Description
O/R
(20)
Local Keypad
Operation
Frequency command is changed to the keypad potentiometer (like as A01 = 0) and
Run command is changed to Standard Operator (like as A02 = 0).
T/R
(21)
Local Terminal
Input Operation
Frequency command is changed to the control terminal input (like as A01 = 1) and
Run command is changed to the control terminal input (like as A02 = 1).
PIDIR(22)
PID Integral
Reset
The accumulated Integral term of the PID controller reset
PIDD(23)
PID Disable
PID control On/Off selection
CM1
Signal source
for input
Common terminal for intelligent input terminals.
P24
External power
supply terminal
for input
External power connection terminal for intelligent input terminals.
F
re
q
u
e
n
c
y
c
o
m
m
a
n
d
in
g
H
Frequency
command
powerterminal
When assign 13[AT signal] to code C01~C06
•
AT signal OFF :
It is possible to command frequency using voltage signal terminal O-L(0~10V)
•
AT signal ON :
It is possible to command frequency using current signal terminal OI-L(4~20mA)
When not assign 13[AT signal] to code C01~C06 It is possible to commend
frequency use the algebraic sum of both the voltage and current input
•
Frequency limit by frequency order method :
Voltage input order(DC 0~10V)
A61 : Minimum frequency(0Hz), A62:Maximum frequency(Enable to A04 Setting
value)
Current input order(4~20mA)
A63 : Minimum frequency(0Hz), Maximum frequency(Enable to A04 Setting value)
O
Frequency
commanding
terminal(voltage
commanding)
OI
Frequency
commanding
terminal(current
command)
L
Frequency
command
common terminal
M
o
n
it
o
r
s
ig
n
a
l
FM
FM output
(voltage)
Analog output frequency monitor/ analog output current monitor/ analog output
voltage monitor/analog output power monitor
AMI
AMI output
(current)
Analog output frequency monitor/ analog output current monitor/ analog output
voltage monitor/analog output power monitor