N700E INSTRUCTION MANUAL
4-20
Func-
code
Name
Run-
time
Edit
Description
Defaults
Other Function
b10
Start frequency
Adjustment
X
Sets the starting frequency for the inverteroutput, range is
0.50 to 10.00Hz in units of 0.01Hz
0.50Hz
b11 Carrier frequency setting
O
Sets the PWM carrier frequency, range is
Refer to ‘Carrier frequency ranges of different types.
(Note8)
(Note7)
b12
Initialization
mode(parameters or trip
history)
X
Select the type of initialization to occur, two option codes:
0.... Trip history clear
1.... Parameter initialization
(exceptional data)
b13 : Country code
A53 : Rated Motor Voltage
0
b13
Country code for
initialization
X
Select default parameter values for country on initialization,
three options,
option codes:
0.... Korea version
1.... Europe version
2.... US version
0
b14
RPM conversion factor
setting
O
Specify a constant to scale the displayed
RPM for [d08] monitor, range is
0.01 to 99.99 in units of 0.01
1.00
b15
STOP key validity during
terminal operation
X
Select whether the STOP key on the
keypad is enabled, two option codes:
0.... stop enabled
1.... stop disabled
0
b16
Resume on FRS
cancellation mode
X
Select how the inverter resumes operation when the free-
run stop (FRS) is cancelled, two options:
0... Restart from 0Hz
1....Restart from frequency detected from real speed
of motor
0
b17 Communication number
X
Sets the communication number for communication,
range is 1 to 32.
1
b18 Ground fault setting
X
Select the function and level of ground fault..
0 : Do not detect ground fault.
0.0~100.0% : Detect ground fault as the % level of
rated current.
0.0
b19
Speed Search Current
Suppression Level
O
Controls the starting current level during speed search
motion on the basis of the motor rated current.
The Current Suppression Level of the controller is set
from 90 % to 180%
100%