6 Man-Machine Interaction
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
Step 2
Insert the USB flash drive into the USB port at the bottom of the SmartLogger.
Step 3
Log in to the app, choose
More
>
System Maintenance
>
Generate Local Maint. Script
on
the main menu page, and generate a boot script file. For details, see the
SUN2000 APP User
Manual
.
Step 4
Replace the boot script file in the upgrade package with the boot script file in the USB flash
drive.
The boot script file in the upgrade package is named
logger_lmt_mgr_cmd.emap
.
Step 5
Insert the USB flash drive into the USB port at the bottom of the SmartLogger. The
SmartLogger automatically executes all commands specified in the boot script file. View the
LED indicator to determine the operating status.
Table 6-5
LED indicator description
Indicator (Silk Screen)
Status
Meaning
ALM
Green off
No local maintenance is in
progress.
Blinking green at long
intervals (1s on and 1s off)
Local maintenance is in
progress.
Green steady on
Local maintenance
succeeds.
Blinking green at short
intervals (0.125s on and
0.125s off)
Local maintenance fails.
Step 6
After upgrade is complete, the SmartLogger automatically restarts.
----End
6.2 NMS Operation
Using the NMS, you can perform firmware upgrade and log export for the SmartLogger. For
details, see
iManager NetEco 1000S User Manual
.
6.3 App Operation
Using the app, you can perform real-time monitoring, alarm query, and device management
for the SmartLogger and southbound devices connecting to the SmartLogger. For details, see
SUN2000 APP User Manual
.