No.
Parameter
Description
Unit
Value Range
Remarks
10
Cutoff power
of
overfrequenc
y derating
Specifies the power
threshold for cutting off
overfrequency derating.
%
[5, 20]
following
condition:
Quit
frequency of
over frequency
derating
≤
Trigger
frequency of
over frequency
derating
<
Cutoff frequency
of overfrequency
derating
.
11
Power
recovery
gradient of
overfrequenc
y derating
Specifies the power
recovery gradient for
overfrequency derating.
%/min
[5, 20]
This parameter is set
to
16
by default if the
Australian AS4777
grid code is selected,
and to
15
by default
if the Italian CEI0-21
or CEI0-16 grid code
is selected.
12
Remote
power
schedule
If this parameter is set
to
Enable
, the inverter
responds to the
scheduling instruction
from the remote port.
If this parameter is set
to
Disable
, the inverter
does not respond to the
scheduling instruction
from the remote port.
If users set this
parameter to
Disable
,
it is recommended that
the SmartLogger
V200R002C10SPC10
0 or later versions be
used to ensure to
precision of gird
scheduling values.
N/A
Disable
Enable
N/A
13
Schedule
instruction
valid duration
Adjusts the duration
within which the
scheduling instruction is
valid.
s
[0, 86400]
If this parameter is
set to
0
, the
instruction is valid
permanently.
14
Maximum
apparent
power
Specifies the output upper
threshold for the
maximum apparent power
to adapt to the capacity
requirements for standard
and customized
transformers.
kVA
[Maximum active
power, Smax_limit]
If the maximum
active power equals
Smax_limit, this
parameter is not
displayed.