SmartLogger2000
User Manual
7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
115
No.
Parameter
Description
Unit
Value Range
Remarks
32
Level-6 OV
protection
Specifies the level-6
overvoltage protection
threshold.
V
[1xVn, 1.5xVn]
Vn represents the
rated voltage.
33
Level-6 OV
protection
time
Specifies the level-6
overvoltage protection
duration.
ms
[50, 7200000]
34
Level-5 UV
protection
Specifies the level-5
undervoltage protection
threshold.
V
[0.15xVn, 1xVn]
Vn represents the
rated voltage.
35
Level-5 UV
protection
time
Specifies the level-5
undervoltage protection
duration.
ms
[50, 7200000]
36
Level-6 UV
protection
Specifies the level-6
undervoltage protection
threshold.
V
[0.15xVn, 1xVn]
Vn represents the
rated voltage.
37
Level-6 UV
protection
time
Specifies the level-6
undervoltage protection
threshold.
ms
[50, 7200000]
38
Level-3 OF
protection
Specifies the level-3
overfrequency protection
threshold.
Hz
[1xFn, 1.15xFn]
Fn represents the
rated frequency.
39
Level-3 OF
protection
time
Specifies the level-3
overfrequency protection
duration.
ms
[50, 7200000]
40
Level-4 OF
protection
Specifies the level-4
overfrequency protection
threshold.
Hz
[1xFn, 1.15xFn]
Fn represents the
rated frequency.
41
Level-4 OF
protection
time
Specifies the level-4
overfrequency protection
duration.
ms
[50, 7200000]
42
Level-5 OF
protection
Specifies the level-5
overfrequency protection
threshold.
Hz
[1xFn, 1.15xFn]
Fn represents the
rated frequency.
43
Level-5 OF
protection
time
Specifies the level-5
overfrequency protection
duration.
ms
[50, 7200000]
44
Level-6 OF
protection
Specifies the level-6
overfrequency protection
threshold.
Hz
[1xFn, 1.15xFn]
Fn represents the
rated frequency.
45
Level-6 OF
protection
time
Specifies the level-6
overfrequency protection
duration.
ms
[50, 7200000]