15
Maximum
active power
Specifies the output upper
threshold for the
maximum active power to
adapt to various market
requirements.
kW
[0.1, Pmax_limit]
N/A
16
Shutdown at
0% power
limit
If this parameter is set to
Enable
, the inverter shuts
down after receiving the
0% power limit
command. If this
parameter is set to
Disable
, the inverter does
not shut down after
receiving the 0% power
limit command.
N/A
Disable
Enable
N/A
17
Reactive
power
compensation
(Q/S)
Adjusts the inverter
output reactive power.
N/A
(-1.000, 1.000]
This parameter is for
the
SUN2000-100KTL-
USH0 only and
displayed when
Remote power
schedule
is set to
Enable
.
18
Reactive
power output
at night
In some specific
application scenarios, a
power grid company
requires that the inverter
can perform reactive
power compensation at
night to ensure that the
power factor of the local
power grid meets
requirements.
N/A
Disable
Enable
This parameter is
available only when
Isolation
is set to
Input ungrounded
(with TF)
.
7.8.3.4 Setting a Tracking System
If a PV string uses a tracking system with controllers, you can set parameters for the tracking
system over the WebUI.
The parameters vary depending on the controller manufacturer. Set parameters based on site
requirements.
This function is applicable only to 1100 V and 1500 V inverters.
Because of permission restriction, log in as
Advanced User
. Choose
Monitoring
>
SUN2000
>
Tracking System
to access the target page.