8 Power Grid Scheduling
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
189
Figure 8-4
Dry contact remote control
A maximum of 16 levels are supported for the active power derating percentage.
"√" indicates a low level. When connecting to GND1, the four DI ports of the SmartLogger are
low-level ports. If not connected, the ports are high-level ports.
The percentage levels of DI1–DI4 should differ from each other. Otherwise, an abnormal command
will be generated.
If the actual input DI signal is inconsistent with that configured on the WebUI, the SmartLogger
controls the SUN2000 to work at full load and generates the
Abnormal Active Schedule
alarm.
8.2.3 Percentage Fix Limitation
The SmartLogger provides simplified active power percentage configuration as well as power
control automation, that is, to automatically adjust the active power derating percentage in
different periods of the day.
If the maximum power output of the inverter needs to be controlled, set
Active power control
mode
to
Percentage fix limitation
.