7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
137
No. Parameter
Function
Value
Description
3
PV type
Specifies the type
of the PV module
used in the PV
plant. For details
about the PV
module type,
consult the
manufacturer.
P-type
Select this value if the PV module type is P. In this
case, the PID module output voltage is positive.
N-type
Select this value if the PV module type is N. In this
case, the PID module output voltage is negative.
4
PV/PE offset
voltage
Specifies the DC
output voltage
when the offset
mode is set to
PV/PE.
0–200 V
It is recommended that the offset voltage be set to a
value ranging from 50 V to 200 V.
5
Operation
Mode
Specifies whether
the PID module is
currently working
in normal or
commissioning
mode.
Commissi
oning
In commissioning mode, if you need to set the
output mode to
PV/PE
or
N/PE
, set
Output
enabled
to
Enable
. The PID module delivers output
voltages based on the value of
Commissioning
output voltage
.
NOTE
To check whether the PID module functions properly, it is
recommended that
Operation mode
be set to
Commissioning
upon first power-on.
Normal
In normal mode, the PID module operates
automatically after the PID module, inverter, and
SmartLogger communicate with each other properly.
NOTE
After checking that the PID module functions properly, set
Operation mode
to
Normal
.
6
Commissioni
ng output
voltage
Specifies the
output voltage
when
Operation
Mode
or
Working
mode
is set to
Commissioning
.
PID01:
0–500 V
It is recommended that the commissioning voltage
for the 1000 V/1100 V inverter be set to a value
ranging from 50 V to 400 V.
SmartPID
2000:
0–800 V
It is recommended that the commissioning output
voltage for the 1000 V/1100 V inverter be set to a
value ranging from 50 V to 400 V, and that the
commissioning output voltage for the 1500 V
inverter be set to a value ranging from 50 V to 600
V.
NOTE
After this parameter is set and the output from the PID
module becomes stable, use a multimeter that is set to the
DC position to measure the three-phase (A, B, and C)
voltages of the power grid to the ground, and check
whether the voltages are the same as the configured values.
7
Maximum
DC voltage
Specifies the
PV-PE voltage
when the normal
operation mode is
used.
500–1500
V
If the PV module type is P, the parameter value
indicates the highest DC voltage between PV+ and
PE. If the PV module type is N, the parameter value
indicates the highest DC voltage between PV– and
PE.