SmartLogger2000
User Manual
7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
110
No.
Parameter
Description
Unit
Value Range
Remarks
3
PQ mode
If
PQ mode 1
is selected,
the maximum AC output
power equals the
maximum apparent power.
If
PQ mode 2
is selected,
the maximum AC output
power equals the rated
output power.
N/A
SUN2000-36K
TL: (Pmax = 40
kW) and PQ
mode 2 (Pmax
= 36 kW)
SUN2000-42K
TL: PQ mode 1
(Pmax = 47
kW) and PQ
mode 2 (Pmax
= 42 kW)
SUN2000-50K
TL-M0 and
SUN2000-60K
TL-M0: PQ
mode 1 and PQ
mode 2
This parameter is
supported by the
SUN2000-36KTL,
SUN2000-42KTL,
SUN2000-50KTL-M0,
and
SUN2000-60KTL-M0.
4
Auto start
upon grid
recovery
Specifies whether to allow
the inverter to
automatically start after
the power grid recovers.
N/A
Disable
Enable
This parameter is set to
Disable
by default if
the Japanese grid code
is selected.
5
Grid
connection
duration after
power grid
recovery
Specifies the waiting time
for inverter restart after the
power grid recovers.
s
[0, 900]
The value range is [150,
900] if the Japanese
grid code is selected.
6
Grid
reconnection
voltage upper
limit
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid voltage is
higher than the upper
limit.
V
[100%Vn,
136%Vn]
Vn represents the rated
voltage.
7
Grid
reconnection
voltage lower
limit
The standards of certain
countries and regions
require that the inverter
must not connect to the
power grid when the
power grid voltage is
lower than the lower limit.
V
[45%Vn, 95%Vn]