IDS1000 Container Data Center
User Manual
1 Configuration Description
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
Figure 1-1
Fire extinguishing system network diagram
Table 1-1
Functions of the components in the fire extinguishing system
Compone
nt Name
Appearance
Function
Gas
extinguishin
g controller
Controls the fire extinguishing system and
reports fire alarm signals.
VESDA
Detects smoke at an early stage, displays the
smoke density and alarm severities, and reports
these information to the monitoring system.
VESDA
power box
Supplies power to the VESDA.
Gas
extinguishin
g
equipment
Stores and releases an extinguishing agent.
Fire
extinguishin
g pipe
Transports an extinguishing agent swiftly and
evenly to the entire protected zone to
extinguish fire in total flooding mode.