IDS1000 Container Data Center
User Manual
3 Power-On Commissioning
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
25
Step 4
Commission the pressure annunciator.
1.
Reset the gas extinguishing controller to automatic and disconnect the cables from the
solenoid valve.
2.
Short-circuit the pressure annunciator cables (red and black), as shown in
The gas release indicator should light up.
Figure 3-18
Short-circuiting the pressure annunciator terminals
Step 5
Commission the emergency startup/abort switch.
The panel of the emergency startup/abort switch is for one-time use only. Before the
commissioning, remove the panel to perform an operation on the emergency startup/abort
switch directly, as shown in
Reset the emergency startup/abort switch after the commissioning (the switch is bounced up
and not pressed).