IDS1000 Container Data Center
User Manual
5 Alarm Reference
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
34
5
Alarm Reference
Alarm
Alarm
Severit
y
Alarm
Type
Impact on the
System
Solution
Gas
extinguish
ing
controller
communic
ation
failure
Critical
Event
The fire
extinguishing
system cannot
be monitored.
See the documents delivered with the
gas extinguishing controller.
Fire
extinguish
ing
hardware
fault
Critical
Event
The fire
extinguishing
system does not
work.
1.
Check whether the fire
extinguishing components are in
good condition and properly
connected.
If yes, contact Huawei
technical support.
If no, go to
2.
Rectify the fault and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei technical
support.
Fire
extinguish
ing
triggered
Critical
Alarm
The fire
extinguishing
equipment has
released
extinguishing
agents into the
protected zone
of the container.
Check whether a fire is present in the
container.
If yes, fire extinguishing cylinders are
triggered. Wait for the fire
extinguishing system to respond.
If no, check whether fire
extinguishing cylinders are triggered.
If the fire extinguishing cylinders
are triggered, press the shutdown
button on the emergency
startup/abort switch to stop fire