3 Power-On Commissioning
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
After the short-circuiting, a smoke detector loop alarm is triggered, and the loop 1
indicator on the gas extinguishing controller panel blinks in red, as shown in
The controller reports a single loop alarm and the fire extinguishing alarm bell alarms.
Figure 3-14
Loop 1 indicator on the gas extinguishing controller panel
You can also use a smoke pistol to release smoke near the smoke detector until the detector is
triggered.
Do not clear the alarm. Proceed to the alarm simulation for the heat detector.
2.
Use a conductor to short-circuit terminals 25 and GND to simulate to trigger the heat
detector, as shown in
Figure 3-15
Short-circuiting terminals 25 and GND