IDS1000 Container Data Center
User Manual
7 Parts Replacement
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49
Step 4
Power on the gas fire extinguishing controller.
Step 5
If the red indicator on the heat detector blinks every 6 seconds, the heat detector is working
properly.
Step 6
Check that the new heat detector is working properly.
----End
Follow-up Procedure
Send the faulty heat detector together with a
Repair Notice
to your local Huawei office for
repair.
7.3 Replacing a Gas Release Indicator
Prerequisites
A gas release indicator is faulty.
Spare gas release indicators are available.
Tools and Materials
Phillips screwdriver
Spare gas release indicators
Gloves
Step ladder
Key to the control box
Impact on the System
None
Procedure
Step 1
Use to screwdriver to loosen the screws that fasten the gas release indicator with its base and
remove the gas release indicator.
Step 2
Connect the cable to a new gas release indicator regardless of the polarity.
Step 3
Check that the new gas release indicator is working properly.
----End
Follow-up Procedure
Send the faulty gas release indicator together with a
Repair Notice
to your local Huawei office
for repair.