FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
31
Step 3
Check the type and quantity of fittings against the packing list. If some fittings are missing or
do not comply with the packing list, record the information and contact your local Huawei
office immediately.
----End
Checking the Outdoor Unit Upon Arrival
Step 1
After the outdoor unit is delivered onsite, check the overtemperature marks.
Overtemperature marks are attached to the outer package and indicate whether the ambient
temperature during transportation exceeds the threshold. If yes, the corresponding temperature
mark background turns black, as shown in
Figure 3-6
Overtemperature mark
If none of the three marks turn black, the transportation meets requirements and the
outdoor unit can be installed after its package is removed as instructed in
If the mark with 60 turns black, unpack the outdoor unit and open its top cover, front
panel, and left front panel. Then check whether there is trace of liquid around the safety
valve connector. If yes, replace the safety valve. If no, install the outdoor unit. For
position of safety valve, see the overtemperature mark.
If the marks with 60 and 65 turn black or all the marks turn black, ask Huawei to confirm
whether the unit can be used.
----End
Unpacking the Outdoor Unit
Step 1
Verify that the outdoor unit package is intact. If any damage is found, notify the carrier
immediately.
Step 2
Remove the package.
1.
Remove the straps, outer packing materials, cushioning materials, and then plastic film.
2.
Check that the outdoor unit exterior is intact and free of collision and scratches. If any
damage is found, notify the carrier immediately.
Step 3
Check the type and quantity of fittings against the packing list. If some fittings are missing or
do not comply with the packing list, record the information and contact your local Huawei
office immediately.
Step 4
After checking that the outdoor unit is intact, remove the four bolts that secure the outdoor
unit to the pallet, as shown in