FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
147
Figure 3-152
T/H sensor layout and DIP switch address (8 cabinets and 3 smart cooling products)
----End
3.11.7 Installing T/H Sensors (in Hot Aisle Containments)
This section describes how to install T/H sensors in hot aisle containments.
Context
The T/H sensor BOM number is 02310NBS.
The number of T/H sensors depends on the number of smart cooling products and
cabinets. Each smart cooling product should be configured with at least one T/H sensor.
For detailed configuration, see the T/H sensor layout.
Procedure
Step 1
Install T/H sensors.
1.
Open the cabinet front door.
2.
Install the T/H sensor base at the 27 U to 28 U position of the post at the cabinet front
door, and then clamp the T/H sensor onto the base.
If battery packs are configured, the installation positions of all T/H sensors can be moved upwards along
the rack rail to avoid interference with battery packs.