FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
4 Cable Routing
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
218
Figure 4-33
Cable route example in the bottom cable routing scenario (3 U PDU for example)
4.5.3 Connecting a PDU2000 Power Cable
Procedure
Step 1
Connect the cord end terminal on the IT cabinet output power cable routed out of the
Converged Cabinet to the PDU2000 cable port in the IT cabinet, as shown in