FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
A Appendix
Issue 10 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
278
No.
From
To
Remarks
sensor
standalone AI/DI module
3
ATS
COM1/12 V port on the
ECC800
Factory-installed
4
FE_1 port on the first
smart cooling product
LAN_1 port on the
ECC800
Factory-installed
5
WiFi module
USB port on the ECC800
Factory-installed
6
FE_1 port on the
second smart cooling
product
LAN_2 port on the
ECC800
Factory-installed
7
WAN_2 port on the
ECC800
FE_2 port on the smart
ETH gateway
Connected onsite
8
53.5VDC_OUT2 port
in the rear of the
ECC800
PWR_OUT port on the
smart ETH gateway
Connected onsite
9
FE_2 port on the third
smart cooling product
Any PoE port on the smart
ETH gateway
Connected onsite
10
PoE port on the first
iBOX
Any PoE port on the smart
ETH gateway
Connected onsite
11
PoE port on the
second iBOX
Any PoE port on the smart
ETH gateway
Connected onsite
12
FE port on the camera
Any PoE port on the smart
ETH gateway
Connected onsite
13
UPS
COM2/12 V port on the
ECC800
Factory-installed
14
Temperature sensor
AI/DI_2 port on the
ECC800
Factory-installed
15
Water sensor
AI/DI_4 port on the
ECC800
The cable has been
connected to the AI/DI_4
port on the ECC800
before delivery.
16
Smoke detector
AI/DI_1 port on the
ECC800
The cable has been
connected to the AI/DI_1
port on the ECC800
before delivery.
17
Fan power contactor
DO_1 port on the ECC800 Factory-installed
18
SPD
AI/DI_3 port on the
ECC800
Factory-installed
19
COM_IN port on the
standalone AI/DI
module
COM3/12 V port on the
ECC800
Connected onsite