8.3.8.5.6.9 ABB Melody (LF/CR)
Below the ABB Melody DataString is described.
8.3.8.5.6.9.1 Specified Settings
Required:
The following settings are required for the synchronization:
•
Output every minute
•
Output without second forerun
•
Output without ETX on the second change
•
UTC time
•
9600 baud, 8 bit, 2 stop bit, parity even
8.3.8.5.6.9.2 Structure
Character No.
Meaning
Hex-Value
1
STX (start of text)
$02
2
status (internal clock status)
$30-39, $41-46
3
day of the week (1=Monday ... 7=Sunday)
for UTC time bit 3 is set to 1 in the day of the
week
$31-37
4
tens hour
$30-32
5
unit hour
$30-39
6
tens minute
$30-35
7
unit minute
$30-39
8
tens second
$30-36
9
unit second
$30-39
10
tens day
$30-33
11
unit day
$30-39
12
tens month
$30-31
13
unit month
$30-39
14
tens year
$30-39
15
unit year
$30-39
16
LF (line feed)
$0A
17
CR (carriage return)
$0D
18
ETX (end of text)
$03