SCS Series Manual —
P/N 15712:L 7/18/16
91
Building-Specific Operation and Programming Examples
The SCS⁄SCE
Point assignments for SCS at address 5:
Since an SCE is not used at address 5, switches 9-16 are not used. Subsequently protocol points 33-64 are unused and are assigned the soft-
ware type ID ACON.
Point assignments for the SCS⁄SCE pair at address 6 and for the pair at address 7:
Point Assignments:
classification
type ID
Point Assignments:
classification
type ID
1
(CON
ON⁄OP
)
needed
ACON
17
(CON
ON⁄OP
)
unused
ACON
2
(CON
OFF⁄CL
)
unneeded
-
18
(CON
OFF⁄CL
)
unused
ACON
3
(VER
ON⁄OP
)
needed
AMON
19
(VER
ON⁄OP
)
unused
ACON
4
(VER
OFF⁄CL
)
unneeded
-
20
(VER
OFF⁄CL
)
unused
ACON
5
(CON
ON⁄OP
)
needed
ACON
21
(CON
ON⁄OP
)
unused
ACON
6
(CON
OFF⁄CL
)
unneeded
-
22
(CON
OFF⁄CL
)
unused
ACON
7
(VER
ON⁄OP
)
needed
AMON
23
(VER
ON⁄OP
)
unused
ACON
8
(VER
OFF⁄CL
)
unneeded
-
24
(VER
OFF⁄CL
)
unused
ACON
9
(CON
ON⁄OP
)
needed
ACON
25
(CON
ON⁄OP
)
unused
ACON
10
(CON
OFF⁄CL
)
unneeded
-
26
(CON
OFF⁄CL
)
unused
ACON
11
(VER
ON⁄OP
)
needed
AMON
27
(VER
ON⁄OP
)
unused
ACON
12
(VER
OFF⁄CL
)
unneeded
-
28
(VER
OFF⁄CL
)
unused
ACON
13
(CON
ON⁄OP
)
needed
ACON
29
(CON
ON⁄OP
)
unused
ACON
14
(CON
OFF⁄CL
)
unneeded
-
30
(CON
OFF⁄CL
)
unused
ACON
15
(VER
ON⁄OP
)
needed
AMON
31
(VER
ON⁄OP
)
unused
ACON
16
(VER
OFF⁄CL
)
unneeded
-
32
(VER
OFF⁄CL
)
unused
ACON
Point Assignments:
classification
type ID
Point Assignments:
classification
type ID
1
(CON
ON⁄OP
)
needed
ACON
17
(CON
ON⁄OP
)
needed
ACON
2
(CON
OFF⁄CL
)
unneeded
-
18
(CON
OFF⁄CL
)
unneeded
-
3
(VER
ON⁄OP
)
needed
AMON
19
(VER
ON⁄OP
)
needed
AMON
4
(VER
OFF⁄CL
)
needed
AMON
20
(VER
OFF⁄CL
)
needed
AMON
5
(CON
ON⁄OP
)
needed
ACON
21
(CON
ON⁄OP
)
needed
ACON
6
(CON
OFF⁄CL
)
unneeded
-
22
(CON
OFF⁄CL
)
unneeded
-
7
(VER
ON⁄OP
)
needed
AMON
23
(VER
ON⁄OP
)
needed
AMON
8
(VER
OFF⁄CL
)
needed
AMON
24
(VER
OFF⁄CL
)
needed
AMON
9
(CON
ON⁄OP
)
needed
ACON
25
(CON
ON⁄OP
)
needed
ACON
10
(CON
OFF⁄CL
)
unneeded
-
26
(CON
OFF⁄CL
)
unneeded
-
11
(VER
ON⁄OP
)
needed
AMON
27
(VER
ON⁄OP
)
needed
AMON
12
(VER
OFF⁄CL
)
needed
AMON
28
(VER
OFF⁄CL
)
needed
AMON
13
(CON
ON⁄OP
)
needed
ACON
29
(CON
ON⁄OP
)
needed
ACON
14
(CON
OFF⁄CL
)
unneeded
-
30
(CON
OFF⁄CL
)
unneeded
-
15
(VER
ON⁄OP
)
needed
AMON
31
(VER
ON⁄OP
)
needed
AMON
16
(VER
OFF⁄CL
)
needed
AMON
32
(VER
OFF⁄CL
)
needed
AMON