3. Fieldbus Integration With Experion System
3.8. Block Instantiation Support
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
87
July 2010
Honeywell
The
Type
function in Control Builder supports the functions associated with instantiable
blocks in fieldbus devices with single capability levels. It lets you build block types for
devices that support block instantiation that include both the fixed function blocks and
the instantiable function blocks. This means you can view the instantiable blocks as part
of the device's block hierarchy in the
Library
tab of Control Builder. The icon for an
instantiable function block has a slash across it and a letter "I_" tag prefix as illustrated
below, so you can easily distinguish it from a fixed function block.
ATTENTION
A manufacturer may choose to define Transducer blocks as
instantiable
instead of fixed. In this case, be sure you
instantiate
a Transducer block for
each physical sensor that is to be used in the device. A Transducer block
usually corresponds to a physical sensor in the vendor's device.
Instantiable block implementation considerations
The following table summarizes considerations that are unique to implementing control
strategies that include fieldbus devices with optional instantiated blocks. Please use these
considerations to supplement the appropriate procedures in the remainder of this
document that are tailored to fieldbus devices with only fixed function blocks including
resource and transducer blocks.
If you want
to . . .
Then,
Notes and References