5. Configuration
5.5. Loading Components Online
208
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
If the Device
ID is . . .
And, the Device
State Is . . .
Then, the matching rule is . . .
Operational
The device ID (DEV_ID), physical device tag
(PD_TAG), and node address (ADDR) must
match those specified through configuration in
Control Builder. Any mismatch results in an
error.
Not specified.
Initialized
The physical device tag (PD_TAG) must match.
If the desired node address (ADDR) is not in
use, FIM will assign it to the device.
Operational
The physical device tag (PD_TAG) and node
address (ADDR) must match those specified
through Control Builder. Any mismatch results in
an error.
Loading a CIOM-A FIM and its Links
The following procedure outlines the typical steps used to "load" a CIOM-A FIM
through the Project tab in Control Builder. It assumes that the FIM and its associated
RTP are installed and capable of communicating with the system.
TIP
If present, it is a good idea to load the CPM and its CEE first to verify the
supervisory communications path.
Step Action
Result
1
Check that the OK LED on the front of
the CIOM-A FIM is flashing and the
numbers 1 and 2 are sequencing in the
left-hand LED on its front panel display.
Confirms that the designated CIOM-A
FIM is operating.
(If ALIV appears in the CIOM-A FIM's
front panel display, you must load the
CIOM-A FIM's personality firmware
before proceeding.)