5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
142
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Description (EDD) files for the fieldbus device either on a disk supplied by the
manufacturer or downloaded from the vendor's web site. This means you can
make a device block type without being connected to a device. You can skip
this procedure, if a block for the given device type already exists in the
Control Builder
Library
database.
The DD files are normally stored in a directory called Release. This directory
must include these three files:
The *.FFO file is the DD binary, or *.FF5 file is the EDD binary file
The *.SYM file is the device symbol file
The *.CFF file is the device capability file.
ATTENTION
With R400, Experion supports DD files and EDD files and continues to
process the DD to create a device block type in the Control Builder library
Step Action
1
On the
File
menu, click
New
->
Type
->
Fieldbus Device
.
2
In the
Select Device Type
dialog box, Click
to browse for the applicable
DD file location in the Device DD Files box.
Or
In
Device List
box, click the device you want to add to the Control Builder
Library.