11. Appendix B
11.1. Standard Function Block Parameters
480
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
FF Data Type
DS-82
Range
Usage
C/Simulate
Length
11
Valid Views
Storage
Dynamic
Remarks
The data type consists of simulate and transducer floating
point value and status and a simulate enable/disable
discrete. It uses the following five elements.
1: Simulate Status
2:Simulate Value
3: Transducer Status
4: Transducer Value
5: Simulate Enable/Disable
SIMULATE_D
Classification
Record
Description
Allows the transducer discrete input or output to the block
to be manually supplied, when SIMULATE is enabled.
When SIMULATE is disabled, the simulate value and status
track the actual value and status.
FF Data Type
DS-83
Range
Usage
C/Simulate
Length
5
Valid Views
Storage
Dynamic
Remarks
The data type consists of a simulate and transducer
discrete value and status and a simulate enable/disable