3. Fieldbus Integration With Experion System
3.6. Notification Scheme
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
77
July 2010
Honeywell
Enumeration Description
Alarm/Event
Type
WRITE
Write Protect Change Alarm
RBWPCHNG
(Write Lock)
UPDATE
Link Object Update Event
FBLOCHNG
(Link Object
Changed)
UPDATE
Trend Object Update Event
No Action
Loading alarm conditions
After configuring the alarm conditions, you must load the saved conditions to the FIM.
Conditions are loaded only after loading only during loading the device. For more
information on loading the conditions, see Loading a CIOM-A FIM and its Links.
ATTENTION
Before loading, turn off the device blocks as it can affect the execution of
associated control strategies.
When you perform device like replacement, advanced alarming conditions
are also loaded from Project mode configuration when the device is
loaded.
When you change the device’s template with an unlike template
replacement, all advanced alarm configuration settings are loaded from
the replacement template.
When you commission the device using Commission Without
Reconfiguration, the device automatically loads the settings from the
selected device template. However, if there are multiple templates that
match the device profile and revision information, you must select the
template before commissioning.
Alarm server operation
User defined conditions are configured to generate the system alarm.
System Alarm: System alarms appear in the System Status Display. The alarm attributes
are set as follows:
Attribute Value
Source Device
tag