6. Operation
6.2. Foundation Fieldbus Detail Displays/Faceplates
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
245
July 2010
Honeywell
AI (Analog Input)
DO (Digital Output)
DI (Digital Input)
AO (Analog Output)
MAI (Multiple Analog Input)
Note that the FF Detail Displays and faceplates are not applicable for mixed modes (FF
AI -> CEE PID -> FF AO).
REFERENCE - INTERNAL
Refer to the following documents for more information:
HMIWeb Display Building Guide
for more information on creating
displays.
Server and Client Configuration Guide
for more information on configuring
faceplates.
Detail Displays contents based on FF control points loading
The FF control points can be loaded to FFLINK environment or CEE (C300 or C200)
environment. However, the contents in the Main tab display vary based on whether the
point is loaded to the CEE environment or to the FFLINK.
Naming conventions for Detail Displays
You need to follow the conventions such as block name, Point Detail Display, and Group
Detail Display to view the FF Detail Displays.
The following table lists the conventions to be followed to view the FF Detail Displays.
Block name
Point detail display
Group detail display
AI sysdtlffaia
sysdtlffai_fp
AO sysdtlffaoa
sysdtlffao_fp
DI sysdtlffdia
sysdtlffdi_fp
DO sysdtlffdoa
sysdtlffdo_fp
PID sysdtlffpida
sysdtlffpid_fp