11. Appendix B
11.1. Standard Function Block Parameters
430
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Range
1 to Manufacturer Limit
Usage
C/Channel
Length
2
Valid Views
VIEW_4
Storage
Static
Remarks
The initial value is 0.
CLR_FSTATE
Classification
Simple Variable
Description
Serves as a switch to reset/clear the device fault state state
after the fault condition is cleared.
FF Data Type
Unsigned 8
Range
1: Off
2: Clear
Usage
C/Contained
Length
1
Valid Views
Storage
Dynamic
Remarks
The operator can control PROGRAM or LOCAL access to
these values.
CONFIRM_TIME
Classification
Simple Variable
Description
Defines the time between retries of alert reports.
FF Data Type
Unsigned 32
Range
Positive