18. Appendix I
18.2. Description
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
547
July 2010
Honeywell
Tab
Parameter Default
Value
Description
DLPdu Physical Layer
Overhead
(LMLSTREC.PHLO)
4
Indicates the configured Data
Link Protocol Data Units
(DLPDU) Physical Layer
Overhead (PhLO) value. The
DLE uses it to account for the
Physical Layer induced delay
between the end of the last
octet of one DLPDU, as it
appears on the link, and the
beginning of the first octet of
any other DLPDU, as it appears
on the link. It is measured in
units of one octet-duration. Its
range is 2 to 63.
Max Response Delay
(LMLSTREC.MRD)
10
Indicates the configured
maximum response delay value.
It is a measure, in units of one
slot time, greater than the worst-
case period of
local
Physical
Entity inactivity that a DLE can
observe. The DLE uses it to
record the Link's maximum
response delay. Its range is 1 to
11.
First Unpolled Node
ID
(LMLSTREC.FUN)
41
Indicates the first unused node
address value. It is the first node
address of a series of
consecutive node addresses,
which are to be omitted from the
orderly probe of node addresses
for DLE's not specified by the
local link live list. Its range is 21
to 247.
Summary of Contents for Experion PKS Series A
Page 242: ......
Page 559: ......
Page 560: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...